Fire Extinguisher - an overview (2024)

Emergency management and security

Ian Sutton, in Process Risk and Reliability Management, 2010

Portable Fire Extinguishers

Portable fire extinguishers include both self-contained fire extinguishing equipment that can be carried by one person and wheeled units that can be handled by one or two people. Due to their limited capacity, portable fire extinguishers are designed to control fires that are just starting or that are of limited size.

Location

Portable fire extinguishers need to be located near the equipment to be protected, but not so close that they can become involved in the fire or that a person cannot reach them. The suggested distance from their point of use is between 5 and 15m. From any grade level point in a process plant, the maximum horizontal distance to a dry chemical extinguisher should not exceed 15m. Extinguisher locations should be conspicuous, clearly marked, and visible from several directions. The locations should not be blocked with materials or equipment that might conceal or impede access to them.

Types

Table 11.4 provides guidance regarding the selection of portable extinguishers.

Table 11.4. Selection of Portable Fire Extinguishers

Class A – ordinary combustible hazards
Water can be used. Multipurpose dry chemical may be considered for some warehouse facilities and offices where lightweight fire extinguishers are desirable for easier handling.
Class B – flammable liquids and gases
The following fire extinguishing materials can be used:

Dry chemical

Carbon dioxide

Multipurpose dry chemical

Class C – electrical hazards and delicate electronic equipment

Carbon dioxide

Dry chemical (an effective agent but difficult to cleanup and may damage the equipment)

Water extinguishers

The superior cooling capacity of water over other extinguishing agents makes it particularly effective on fires involving ordinary combustibles such as wood, paper, fabrics, or rubber. Water extinguishers do not require extensive cleanup after use and they are non-corrosive to electronic circuitry, unlike dry chemical extinguishers. When water extinguishers are subject to freezing weather antifreeze is added.

Carbon dioxide extinguishers

Carbon dioxide (CO2) is stored in extinguishers in the liquid phase. It vaporizes when released thereby smothering a fire by excluding the air (oxygen) needed for combustion. As already noted, Carbon dioxide extinguishers are preferable to water or dry chemical extinguishers where water damage and fouling of delicate electrical, electronic, or laboratory equipment cannot be tolerated or where cleanup is a consideration.

If a CO2 extinguisher is discharged in a confined space then that space must be ventilated once the fire is extinguished.

Dry chemical extinguishers

Many types of dry chemical extinguishing agents are available. Those shown below are used in the process industries.

Sodium bicarbonate;

Potassium bicarbonate base (Purple K); and

Monoammonium phosphate.

Sodium bicarbonate was the original dry chemical extinguishing agent. The chemical currently available is a mixture consisting primarily of sodium bicarbonate with various additives to improve flow and storage characteristics. Chief among the additives is a silicone polymer. It is used to prevent moisture absorption and consequent caking of chemical. It works by interrupting the propagation of the flame. Its electrical resistivity is high, and it is nontoxic. This agent may be used for extinguishing fires involving flammable liquids, gases and electrical equipment. It is not effective in extinguishing deep-seated fires in ordinary combustibles.

Potassium bicarbonate chemical, whose physical properties are similar to sodium bicarbonate, is effective at extinguishing fires involving flammable liquids and gases. It is also suitable for use on fires involving electrical equipment. It is not effective in extinguishing deep-seated fires in ordinary combustibles.

Monoammonium phosphate based chemical is effective in controlling and extinguishing fires involving flammable liquids and gases, ordinary combustible materials, and electrical equipment. It is recommended where piped water is not available, where freezing conditions are expected, or where a combination of different classes of hazards exists. It has physical properties similar to the sodium bicarbonate chemical but is more effective on flammable liquid fires. It is corrosive to electronic circuitry. It should not be mixed bicarbonate dry chemicals. A chemical reaction can occur in the extinguisher that generates CO2 and other gases; the pressure buildup could rupture the extinguisher.

Read full chapter

URL:

https://www.sciencedirect.com/science/article/pii/B9781437778052100110

Methods of Fire Suppression

Dennis P. Nolan, in Handbook of Fire and Explosion Protection Engineering Principles for Oil, Gas, Chemical, and Related Facilities (Fourth Edition), 2019

19.1 Portable Fire Extinguishers

Historical evidence indicates that portable (i.e., manually manipulated and operated) fire extinguishers are the most common method of extinguishing a fire in the process industry in the incipient stage. Human surveillance combined with the ability to quickly and effectively react to the beginning of an incipient fire has prevented countless process incidents from developing into large-scale disasters. The objective of providing portable fire extinguishers is to have an available supply of plentiful extinguishers that can be easily used in the early stages of a fire. When these extinguishing means are exhausted or the incipient fire has grown to the point of uncontrollability by manual methods, fixed fire suppression systems and process incident control systems should be activated (e.g., emergency shutdown). Only personnel trained in portable fire extinguisher use should be expected to use them.

Fire Extinguisher - an overview (1)

A portable fire extinguisher is a device used to put out fires of limited size. Portable extinguishers are classified by expected application on a specific type of fire (i.e., A, B, C, or D) and the expected area of suppression. The four types of fires are grouped according to the type of material that is burning. Class A fires are those in which ordinary combustibles such as wood, cloth, and paper are burning. Class B fires are those in which flammable liquids, oils, and grease are burning. Class C fires are those involving live electrical equipment. Class D fires involve combustible metals such as magnesium, potassium, and sodium.

The numerical rating on the fire extinguisher is a relative rating number. It is assigned by recognized testing laboratories for the amount of average fire area that can be extinguished according to methods established by the National Fire Protection Association (NFPA). The rating does not equate to the amount of square feet that can be expected to be extinguished by an individual using the extinguisher.

The classes of portable fire extinguishers manufactured and used in industry are defined below. Other countries have similar classifications (although these may not be exactly the same).

Extinguishers for Class A fires

Class A fire extinguishers are usually water-based. Water provides a heat-absorbing (cooling) effect on the burning material to extinguish the fire. Pressurized water extinguishers use air under pressure to expel the water which is directed with a short hose.

Extinguishers for Class B fires

Class B fires are put out by excluding air, by slowing down the release of flammable vapors or by interrupting the chain reaction of the combustion. Three types of extinguishing agents are typically used—carbon dioxide, dry chemical, and foam water for fires involving flammable liquids, greases, and oils. Carbon dioxide is a compressed gas agent that prevents combustion by displacing the oxygen in the air surrounding the fire. The two types of dry chemical extinguishers include one that contains ordinary sodium potassium bicarbonate, urea potassium bicarbonate, and potassium chloride base agents. The second, multipurpose type contains an ammonium phosphate base. The multipurpose extinguisher can be used on Class A, B, and C fires. Most dry chemical extinguishers use stored pressure to discharge the agent, and the fire is extinguished mainly by the interruption of the combustion chain reaction. Foam extinguishers use an aqueous film-forming foam (AFFF) agent that expels a layer of foam when it is discharged through a nozzle. It acts as a barrier to exclude oxygen from a fire.

Extinguishers for Class C fires

The extinguishing agent in a Class C fire extinguisher must be electrically nonconductive. Both carbon dioxide and dry chemicals can be used for electrical fires. An advantage of carbon dioxide is that it leaves no residue after the fire is extinguished. When electrical equipment is not energized, extinguishers for Class A or B fires may be used. Note that since an extinguisher rated solely for a Class C fire is not manufactured, and an ABC- or BC-rated fire extinguisher will have to be specified for this hazard application.

Extinguishers for Class D fires

A heat-absorbing extinguishing medium is needed for fires in combustible metals. Also, the extinguishing medium must not react with the burning metal. The extinguishing agents, known as dry powders, cover the burning metal and provide a smothering blanket.

The extinguisher label provides operating instructions and identifies the class or classes of the fire on which the extinguisher may be used safely. Approved extinguishers also carry the labels of the laboratories at which they were tested.

Portable fire extinguishers should be positioned in all process facility areas so that the travel distance to any extinguisher is 15m (50ft) or less. They are generally sited on the main walkways or exits from an area, near the high hazard itself and near other emergency devices. They are mounted so individuals can easily retrieve them, typically approximately 1m (2.5ft) from the walking surface with red highlighting at the mounting location.

Read full chapter

URL:

https://www.sciencedirect.com/science/article/pii/B9780128160022000192

Industrial Examples

Mukesh Doble, Anil Kumar Kruthiventi, in Green Chemistry and Engineering, 2007

Fire Extinguishers and Flame Retardants

Traditionally, fire extinguishers have utilized halogens (CFCs), which today are well-known ozone-depleting agents. They also harm aquatic systems and contaminate water supplies. Pyrocool is a nontoxic, biodegradable, fire-extinguishing and cooling agent that can replace the traditional extinguishers, is just as effective in putting out fires, and does not deplete the ozone layer or persist in the environment, unlike CFCs.

Epoxy phenolic molding compounds (EMC) are mixtures of chemicals containing a base polymer resin matrix and various additives. Usually these additives are brominated epoxy resin and antimony oxide, which function as flame retardants. These compounds produce toxic fumes during flame and are also dangerous for the environment. In the last few years research has focused on developing polymers containing halogen-free flame-retardant additives, which lead to compounds containing P, Si, B, N, Al(OH)3, and Mg(OH)2. In addition to their low toxicity, their main advantages are that, in the case of fire, they do not produce dioxin and halogen acids, and they generate low amounts of smoke. Recently the microelectronics industry developed new halogen and antimony-free molding compounds based on phosphorous-based, organic, flame-retardant additives. These materials reduce the presence of toxic elements in the electronic package and the environment. It is known that halogens and other ionic impurities are responsible for metal corrosion under bias, humidity, and high temperatures. Elimination of these compounds in the formulation increases the life of these materials.

Read full chapter

URL:

https://www.sciencedirect.com/science/article/pii/B9780123725325500109

Fires

Daniel A. Vallero PhD, Trevor M. Letcher MSc(Natal), PhD(Natal), BEd(Natal), FRSC, in Unraveling Environmental Disasters, 2013

Dry Powders

Sand is a cheap and useful extinguisher of fires. It acts as a smothering agent separating the fuel from the air. In addition to sand, sodium bicarbonate (NaHCO3) is used as a dry chemical for class A, B, and C fires. Sodium bicarbonate acts in a very different way to sand. It decomposes at 270°C according to the reaction

(7.4)2NaHCO3=H2O+CO2+Na2CO3,Δr=91kJmol-1.

It acts in a number of ways; the decomposition products are water (a good fire-fighting chemical), CO2 (which smothers the fire), and sodium carbonate powder which also acts as an inert smothering agent. Further, the reaction is endothermic, so it absorbs heat from the fire and this helps in reducing the temperature. In a fire extinguisher, the powder is driven out of its container by either nitrogen or CO2 under pressure.

The foregoing thermodynamic factors influence not only the extent and duration of a fire disaster but also the type of damage. For example, the choice of fire extinguishing materials can affect the types of emissions released from the fire. This could entail a trade-off between fire control and emissions that could impact health and environmental quality. We shall now consider some notorious fires that have had disastrous effects on the environment.

Read full chapter

URL:

https://www.sciencedirect.com/science/article/pii/B9780123970268000070

Volume 5

W.T. Tsai, in Encyclopedia of Environmental Health (Second Edition), 2019

Fire Extinguisher or Fire Suppression Agent

Traditionally, halons have been extensively used as effective fire extinguishers in fixed, total flooding systems for protecting sensitive electrical equipment. Owing to the Montreal Protocol, the phaseout of production of halons (i.e., halon 1301 and halon 1211) has been effective in the developed countries since 1994. The regulation stimulated tremendous efforts to search for acceptable replacements and alternatives including perfluorocarbons. Because n-C6F14 is electrically nonconductive and leaves no residue after extinguishment of fire, it has been listed as an acceptable substitute for halon 1211 (CF2ClBr) streaming agents subject to narrowed use limits (i.e., nonresidential uses) according to the SNAP Program as of October 1, 2004.

Read full chapter

URL:

https://www.sciencedirect.com/science/article/pii/B978012409548911348X

Determination of noninsecticidal compounds in soil

T.R. Crompton, in Determination of Toxic Organic Chemicals in Natural Waters, Sediments and Soils, 2019

Perfluorooctane sulphonyl fluoride

These substances are widely applied to the production of water repellents, fire extinguishers and surface coating of paper and textiles in the 1960s because of their perfect surface activity and stability.

This group of compounds has been introduced into the environment in recent years. Because of their lipophilic characteristics they have been detected in human and animal tissue.

In May 2001 the Stockholm Convention on persistent organic compounds was brought into effect. In 2009 perfluorooctane sulphonate and its precursor perfluorooctanoic acid were listed.

Meng et al. [201] determined perfluorooctane sulphenyl fluoride and developed a method using LC with UV and fluorescence detection.

In this study a new method was developed by derivatising perfluorooctane sulphenyl fluoride with 1-naphthol to form 1-naphthylperfluorooctanesulphonate that allowed rapid qualitative and quantitative analysis using LC–UV and LC–FLD. The derivatising product was confirmed from the analyses by proton nuclear magnetic resonance (NMR) and quadrupole-time-of-flight MS. The LC–FLD method demonstrated good linearity in the 1-naphthylperfluorooctanesulphonatelate concentration range from 20µgL−1 to 20ngL−1 with correlation coefficient better than 0.00, and an instrumental detection limit of 1.5pgµL−1.

Read full chapter

URL:

https://www.sciencedirect.com/science/article/pii/B9780128158562000151

Hepatic Toxicology

J.E. Manautou, ... L.M. Aleksunes, in Comprehensive Toxicology, 2010

9.08.3.5.2 Carbon tetrachloride

Carbon tetrachloride (CCl4) is a compound that was previously used as a dry cleaning solvent, a refrigerant, and also in fire extinguishers. Its industrial use has been largely abandoned due to well-documented adverse health effects. Exposure to CCl4 results in centrilobular hepatic necrosis. CCl4 is metabolized by CYP2E1 to the highly reactive trichloromethyl free radical, which causes hepatocellular damage through lipid peroxidation (Manibusan et al. 2007). For more on CCl4 hepatotoxicity, please see Chapter 09.20.

Natkatsukasa et al. (1993) reported increased Mdr1a, Mdr1b, and Mdr2 gene expression in rat liver after toxic CCl4 administration. In another study, CCl4 exposure caused a decrease in Ntcp and Oatp1a1 mRNA levels in rat liver (Geier et al. 2002b). Reduced Oatp1b2 and Ntcp protein expression was also noted. When hepatic efflux transporters were examined during CCl4 toxicity in rats, increased Pgp and decreased Mrp2 protein levels were detected, along with corresponding changes in their transport activity (Song et al. 2003). Analysis of multiple transporters in mice revealed that CCl4 decreased mRNA expression of the basolateral uptake transporters Oatp1a1, Oatp1b2, and Ntcp, and simultaneously increased mRNA levels for the efflux transporters Mrp1, Mrp2, and Mrp4 (Aleksunes et al. 2005). Western blot analysis demonstrated reduced Ntcp and increased Mrp1, Mrp2, and Mrp4 in these mice (Aleksunes et al. 2006). Similar to the expression pattern seen after APAP administration, upregulation of Mrp4 protein was observed in hepatocytes adjacent to the central vein after CCl4 exposure (Figure 9) (Aleksunes et al. 2006). Microarray analysis of livers from rats treated with CCl4 confirmed some of the mouse observations. Gene expression of Mdr1a, Mdr1b, Mrp1, and Mrp4 was increased by CCl4, while the expression of Mrp2, Mrp6, Oct1, and Oat3 was decreased (Okumura et al. 2007).

Read full chapter

URL:

https://www.sciencedirect.com/science/article/pii/B9780080468846010083

Disciplines Involved in Offshore Platform Design

Naeim Nouri Samie MSc Hydraulic Structures, in Practical Engineering Management of Offshore Oil and Gas Platforms, 2016

2.9.3 Passive Protection

Passive and active protections are used in offshore platforms. Active protection is achieved by means of fire water pump, sprinklers, hydrants, hose reels, chemical extinguishers, foams, deluge valves, etc. Passive protection is achieved by providing specifically rated barriers, walls with the required fire rating, special coatings, etc. These walls shall be capable of tolerating temperature increase as per code requirement. They are classified as A-, H-, and J-rated walls. B-rated walls are only comfort insulation. Standard fire temperature and duration as per ISO 834 (EN1364–1) is shown in Table2.10. With temperature in °C and time in minutes, the following formulas represent standard and hydrocarbon fire test curves. ISO standard fire curve is somehow different from ASTM E−119 standard curve.

Table2.10. Standard fire temperature variation

Duration (Min)3510153060
Standard fire Temperature (°C)A502576679738842945
H8879481034107110981100

Standard Fire: T=20+345log(8t+1)

Hydrocarbon Fire: T=20+1080[1−0.325exp(−0.167t)−0.675exp(−2.5t)]

A-rated walls are for general fire case. The selected compartment shall be able to provide structural resistance against normal operational loads and limit heat transfer for a specified duration. For example, A60 means durability for 60min against class A fire. H-rated walls have the same condition against hydrocarbon fires. J-rated walls shall resist jet fires. This is caused by sudden leakage and ignition of gas. In many cases this may be accompanied by blasts. Therefore for J-rated conditions a blast overpressure is also identified. Blast pressure reduces with square root of distance. Blast load for a localized impact is much more than a large area. Detailed safety studies are needed to calculate blast load and specify wall/deck ratings.

Structural steel with special coating systems is needed to achieve the required fire rating. Coating may be applied on structural wall, columns, braces, beams, joints, decks, vessels, piping manifolds, and valves. For valves that require periodic inspection, coating shall be of a removable jacket type. Both type of fixed-shape and flexible jackets are available. Required thickness shall be calculated for each case. The important feature of these coatings is that heat transfer from the face adjacent to the fire to the face adjacent to the metal surface is very much limited.

Read full chapter

URL:

https://www.sciencedirect.com/science/article/pii/B9780128093313000028

Carbon Dioxide

S. Goel, D. Agarwal, in Encyclopedia of Toxicology (Third Edition), 2014

Uses

Carbon dioxide is used in the synthesis of urea, for organic synthesis, in the manufacture of dry ice and aspirin. It is also used in soft drinks, welding, fire extinguishers, and aerosol propellants. CO2 is often used as a pesticide to store grains (at 60% concentration), respiratory stimulant, anesthetic, and euthanizing agent. It is essential in in vitro cell culture environment at 5%, where it dissolves in the culture media to form bicarbonate (HCO3) and acts as a buffer to help maintain the pH of CO2. Industries that use carbon dioxide include fire extinguishing; processing, preserving, and freezing of food; metal working; livestock slaughtering; oil and gas recovery; and foundries. It is also used to produce harmless smoke or fumes on a stage, chill golf ball centers before winding, and fumigate rice.

Read full chapter

URL:

https://www.sciencedirect.com/science/article/pii/B9780123864543002694

Source Identification and Age Dating ofChlorinated Solvents

Robert D. Morrison, Brian L. Murphy, in Introduction to Environmental Forensics (Third Edition), 2015

9.3.4 Carbon Tetrachloride

Compared to other chlorinated solvent products, little historical information regarding manufacturing impurities in carbon tetrachloride is available in the peer-reviewed technical literature. An early use of carbon tetrachloride was as a fire extinguisher fluid; although not a manufacturing impurity, a 1911 patent identified the use of 1.5% by volume oil of amber and the same quantity ofnitrobenzeol (Davidson, 1911; US War Department, 1943). When exposed to heat, however, it was found that carbon tetrachloride produced phosgene gas, which led to the recall of fire extinguishers using carbon tetrachloride in the late 1960s. AUS War Department Technical Manual (TM 9-850) of August 24, 1944, allowed the mixture of TCE (10%) as a freezing point depressant with carbon tetrachloride in fire extinguishers.

Correspondence in the 1924 British Medical Journal identified carbon bisulphide (carbon disulfide) as the most common impurity in carbon tetrachloride (Dale, 1924). The presence of carbon disulfide is not surprising as nearly all of the carbon tetrachloride produced in the United States prior to 1950 was manufactured by the chlorination of carbon disulfide, typically with a catalyst such as ferric chloride (Holbrook, 1991; Doherty, 2000a).

A 1946 article lists, by percent volume, 1,2-dichloroethane (0-2%), TCE (0-1%), PCE (0-1.6%), hexachloroethane (0-0.02%), and 1,1,2,2-tetrachloroethane in commercial grade carbon tetrachloride (Williams, 1946). In 1959, an analysis by Dow Chemical Company of carbon tetrachloride for the purpose of identifying trace impurities identified 1,2-dichloromethane, 2-propanone (acetone), carbon disulfide, chloroform, TCE, and PCE (Kiley and Scheddel, 1959). In 1991, specifications for technical grade carbon tetrachloride carbon tetrachloride were to contain no more than 1 ppm of carbon disulfide, 20 ppm of bromine, and 150 ppm of chloroform if manufactured via the carbon disulfide chlorination method (Holbrook, 1991). In 1994, trichloromethane, carbon disulfide, TCE, and PCE were detected in high-purity carbon tetrachloride (Ogino and Sakai, 1994).

A 2010 analysis of high-purity grade carbon tetrachloride sponsored by the Russian Foundation for Basic Research identified 24 impurities including TCE, PCE, 1,2-DCA, chloroform, benzene, hexachloroethane, and carbon disulphide. For high-purity grade 18-4 TU (Technical Specification 6-09-3219-84) carbon tetrachloride, impurities with the highest concentrations included 1,2-DCA, TCE, and benzene (Krylov etal., 2010). Subsequent testing of a carbon tetrachloride sample and its equilibrated vapor-phase condensate confirmed the presence of PCE, hexachloroethane, and phosgene (see Table 9.5).

TABLE 9.5. Analysis of Carbon Tetrachloride Stock Sample and Condensate of Equilibrium Vapor Phase

ImpurityStock Sample (n = 5)Vapor Phase Condensate (wt %)
Tetrachloroethylene (PCE)(8 ± 3) × 10-7(1.6 ± 0.2) × 10-5
Phosgene(3.3 ± 0.5) × 10-6(1.1 ± 0.2) × 10-6
Hexachloroethane(4.0 ± 0.9) × 10-7< 4 × 10-8

As with other chlorinated solvents, when using manufacturing impurities for forensic purposes it is important to distinguish their presence as a manufacturing impurity versus as a stabilizer or intentional ingredient (Missbach, 1936, 1937a, 1937b, 1937c; Ohlmann, 1945; Davidowich and Leeds, 1964). Although TCE was identified in the 1959 and 2010 samples as a manufacturing impurity, TCE was also intentionally added to carbon tetrachloride as a freezing-point depressant (carbon tetrachloride freezes at -22.9oC and TCE at -89oC) used in fire extinguishers in the 1940s (US War Department, 1944).

Read full chapter

URL:

https://www.sciencedirect.com/science/article/pii/B9780124046962000096

Fire Extinguisher - an overview (2024)

FAQs

Fire Extinguisher - an overview? ›

Fire extinguishers apply an agent that will cool burning heat, smother fuel or remove oxygen so the fire cannot continue to burn. A portable fire extinguisher can quickly control a small fire if applied by an individual properly trained.

What are the 4 types of fire extinguishers? ›

There are four classes of fire extinguishers – A, B, C and D – and each class can put out a different type of fire.

What are fire extinguishers explained simply? ›

A fire extinguisher is a handheld active fire protection device usually filled with a dry or wet chemical used to extinguish or control small fires, often in emergencies.

What is the 4 letter acronym for fire extinguisher? ›

It's easy to remember how to use a fire extinguisher if you can remember the acronym PASS, which stands for Pull, Aim, Squeeze, and Sweep.

What are the 7 parts of a fire extinguisher? ›

The Parts of a Fire Extinguisher
  • Cylindrical Tank.
  • Valve.
  • Carry Handle.
  • Operating Lever.
  • Pull Pin.
  • Tamper Seal.
  • Pressure Gauge.
  • Discharge Hose.
Sep 8, 2020

What is a type ABC fire extinguisher for? ›

Multipurpose Extinguishers

For example, an extinguisher with a BC rating is suitable for use with fires involving flammable liquids and energized electrical equipment. An extinguisher with an ABC rating is suitable for use with fires involving ordinary combustibles, flammable liquids and energized electrical equipment.

What is fire extinguisher ABC vs K? ›

Class K fire extinguishers have a silver/chrome color while Class ABC fire extinguishers are usually red. In terms of contents, Class K fire extinguishers are wet chemical, while Class ABC fire extinguishers are dry chemical.

Do fire extinguishers expire? ›

How long do fire extinguishers last? The average lifespan of a powder, foam or water extinguisher is usually between 10 and 12 years. This is based on the extinguisher being in good condition with no corrosion or damage. After this time, the fire extinguisher should be replaced with a new one.

What does ABC stand for fire? ›

Class A – Fires that involve common combustibles such as wood, paper, cloth, rubber, trash, and plastics. Class B – Fires that involve solvents, oil, gasoline, paints, lacquers and other oil-based products. Class C – Fires that involve energized electrical equipment.

What does fire abcd mean? ›

The three most common types of fire extinguishers are: • Water (APW) • Carbon Dioxide (CO2) • Dry Chemical (ABC,BC,DC) • Wet Chemical.

What does 10 ABC fire extinguisher mean? ›

Fire Extinguisher Classes

Class A puts out ordinary combustible fires (wood, paper, plastic, etc.) Class B puts out flammable liquid fires (oil, gas, petroleum, etc.) Class C puts out electrical fires. Class D puts out combustible metal fires (magnesium, titanium, potassium, sodium, etc.)

What fire extinguisher is most commonly used? ›

The multi-purpose dry chemical fire extinguisher is the most common type of portable fire extinguisher for work and home use. Dry chemical fire extinguishers put the fire out by interrupting the chemical reaction of the fire triangle.

What are the 3 basic steps in using the extinguisher? ›

How to operate a fire extinguisher
  1. Pull (Pin) Pull pin at the top of the extinguisher, breaking the seal. ...
  2. Aim. Approach the fire standing at a safe distance. ...
  3. Squeeze. Squeeze the handles together to discharge the extinguishing agent inside. ...
  4. Sweep.

How do you remember the types of fire extinguishers? ›

"DC" short for "dry chem" • "ABC" indicating that they are designed to extinguish class A,B,and C fires, or • "BC" indicating that they are designed to extinguish class B and C fires. "ABC" fire extinguishers are filled with a fine yellow powder.

What is C type fire? ›

WHAT ARE CLASS C FIRES? A class C fire is one in which an energized electrical element is the cause of the fire. “Energized” means that the electrical component (whether electrical appliance, wiring, device, etc.) is connected to a power source.

What is an example of a Class A fire? ›

Class A: Ordinary solid combustibles such as paper, wood, cloth and some plastics.

Can ABC fire extinguisher be used on wood? ›

Class A fires involve ordinary materials such as paper, cloth, wood, cardboard, foam, and other rubbish and debris. Use a Class A or Class ABC fire extinguisher on this type of fire.

Can I use an ABC fire extinguisher on a grease fire? ›

Other ways to put out grease fires…

Use a class B or BC or ABC fire extinguisher. A Fire Extinguisher will release a-lot of pressure, so start at a distance away and move towards the fire, rather than up-close spraying directly on to the burning grease which could tip the pan and spread the fire.

What kind of fire extinguisher for kitchen? ›

Kitchen Fire Safety

Fire extinguishers are marketed for use on residential kitchen fires and carry a Class B rating. These types of fire extinguishers generally use high-volume, low-velocity delivery of the extinguishing agent to prevent splattering and spreading of the burning liquid grease.

What is the first thing you must do before using a fire extinguisher? ›

Before operating the fire extinguisher, make sure you have a clear evacuation path. If you cannot put out the fire, you'll need to make a safe exit. Consider this when determining where to store your fire extinguisher, and make sure you'll have multiple exit options nearby after you retrieve it.

What is the first thing to know about fire extinguishers? ›

The first thing to know about fire extinguishers is that you must be trained and authorized to use one in an emergency. The point is that most people have never used one and it takes some training and practice to use one properly.

How far away should you stand when using a fire extinguisher? ›

Aim low: Standing 6 to 8 feet (2-3 meters) away from the fire, point the extinguisher nozzle at the base of the fire--the lowest point of the fire nearest you. Extinguishers are designed to be operated in an upright position. Always hold the extinguisher vertically.

What not to do with a fire extinguisher? ›

What should you not do when using a fire extinguisher?
  1. Don't ignore the instructions on the fire extinguisher. ...
  2. Don't use the wrong type of extinguisher for the wrong type of fire. ...
  3. Don't rush towards the first unprepared. ...
  4. Don't stand too close to burning liquid when attempting to extinguish it.
Aug 1, 2019

Where not to put a fire extinguisher? ›

Fire extinguishers should never be more than 75 ft. away from a Class A (ordinary combustibles) hazard, and no more than 50 ft. from a Class B (flammable liquids) hazard. When you mount a fire extinguisher to a wall, keep it high enough so kids can't reach it, near an exit, and away from any kind of heat source.

Where is the best place to put an extinguisher? ›

Accessible: “Extinguishers should be placed where they are readily accessible in the event of a fire, which typically includes normal paths of travel.” Visible: “If visual obstructions cannot be avoided, then arrows, lights or signs are needed to help indicate where a fire extinguisher is located.”

Will a 20 year old fire extinguisher still work? ›

Although they don't have a true "expiration date," traditional fire extinguishers generally have a 10-12 year life expectancy. Disposable (non-rechargeable) fire extinguishers should be replaced every 10 years.

How do I know if my fire extinguisher is empty? ›

There are essentially two types of fire extinguishers: rechargeable and disposable. You can check which kind you have by checking the gauge. Rechargeable ones will read either “charge” or in the green, “overcharge” or “recharge,” and disposable ones will read “full” or “empty.”

How do you know if your fire extinguisher is still good? ›

Most fire extinguishers come with a pressure gauge that indicates the pressure level of the internal contents. If the gauge needle falls too low (you can tell if it is outside the green zone on the gauge), you know it's time to replace your extinguisher.

What are the 3 elements of fire? ›

Oxygen, heat, and fuel are frequently referred to as the "fire triangle." Add in the fourth element, the chemical reaction, and you actually have a fire "tetrahedron." The important thing to remember is: take any of these four things away, and you will not have a fire or the fire will be extinguished.

Can a fire extinguisher be used on a small paper fire? ›

Fire extinguishers with a Class A rating are effective against fires involving paper, wood, textiles, and plastics. The primary chemical used to fight these fires is monoammonium phosphate, because of its ability to smother fires in these types of materials.

What does 2A mean on fire extinguisher? ›

The Class A size rating represents the water equivalency. Each number represents 1 ¼ gallons of water. For instance, 2A means the extinguisher is just as effective as 2 ½ gallons of water. 4A is equivalent to 5 gallons of water. The Class B size rating indicates the square footage the extinguisher can cover.

What is the Charlie side? ›

Alpha, Bravo, Charlie, Delta – these terms are used to designate the sides of a structure. Generally speaking, the “alpha” side is the front of the structure, the “bravo” side is the left side of the structure, “charlie” is the back of the structure and “delta” is the right side of the structure.

What is the A side of a fire? ›

Side A (Alpha) is the front of. the building usually the side with the building/house.

How do you put out a Class B or C fire? ›

The five common methods of extinguishing fires are cooling with water for Class A fires, smothering with a chemical for Class B fires, starving (cutting off the supply of oxygen) for class C fires, breaking the chain reaction of fire for Class D fires, and Chemical fire extinguishers for Class K fires.

What is Type B fire extinguisher? ›

Class B fire extinguisher – water mist, foam, dry powder, CO2, some wet chemical. Class C fire extinguisher – water mist, dry powder.

What type of fire does CO2 put out? ›

What is a carbon dioxide fire extinguisher used for? Carbon dioxide fire extinguishers are mainly used for two specific fire classes: Class B and electrical fires (Electrical risks). A Class B fire usually involves some sort of flammable liquid such as petrol or oil (not cooking oils or fats).

What is 2A 10B C fire extinguisher? ›

The Amerex 5 lbs Multi-Purpose ABC Dry Chemical Fire Extinguishers (2A:10B:C) are 3-in-1 fire extinguishers that can effectively stop fires involving ordinary combustibles, flammable gas and liquids, and electrical equipment in small to medium spaces such as offices, schools, hospitals, homes, and cars.

Which fire extinguisher removes oxygen? ›

Carbon dioxide extinguishes work by displacing oxygen, or taking away the oxygen element of the fire triangle. The carbon dioxide is also very cold as it comes out of the extinguisher, so it cools the fuel as well.

What extinguisher a fire most quickly? ›

HOT WATER EXTINGUISHES FIRE MORE QUICKLY. 2.

What kind of fire extinguisher for electrical room? ›

In the case of electrical fires, also known as energized electrical fires, class C fire extinguisher is needed to put it out.

What is the golden rule of fire? ›

When considering whether to tackle a small fire yourself if you discover one, always bear in mind the golden rule of fire safety; If in doubt, get out, stay out and call the Fire Brigade immediately.

What are the two golden rules to remember when fighting a fire? ›

  • In the event of a fire or other emergency, remember four golden rules: ...
  • Emergency Services: Call no matter how small.
  • Save these numbers on your cell phone: ...
  • Extinguish: Only try to extinguish if safe to do so. ...
  • Fire Action! ...
  • * Using a Fire Extinguisher.
  • P – Pull the pin. ...
  • EMERGENCY NUMBERS.

What size fire is too big to tackle? ›

Make sure the fire is small.

The flames should never be taller than you and should not cover an area that is bigger than 60 square feet. 60 square feet is about the size of a king size bed (42.15 square feet), so don't try to tackle a fire that is much bigger than that.

What are 3 things to look for when inspecting a fire extinguisher? ›

Confirm the extinguisher is visible, unobstructed, and in its designated location. Verify the locking pin is intact and the tamper seal is unbroken. Examine the extinguisher for obvious physical damage, corrosion, leakage, or clogged nozzle.

What are the 4 types of fire extinguishers and their uses? ›

Class A - Suitable for paper, wood & textiles. Class B - Suitable for flammable liquids. Class C - Suitable for flammable gasses. Class F - Suitable for cooking oil and fat.

What are the different types of fire extinguisher OSHA? ›

The three most common types of fire extinguishers are: air pressurized water, CO2 (carbon dioxide), and dry chemical.

What are the 3 most common types of fire extinguishers? ›

According to OSHA, air pressurized water, carbon dioxide (CO2) and dry chemical are the three most common types of fire extinguishers, with wet chemical extinguishers also used often.

What fire extinguisher for all fires? ›

Powder extinguishers are a good multi-purpose fire extinguisher because they can be used on Class A, B and C fires. They can also be used on fires involving electrical equipment however, they do not cool the fire so it can re-ignite.

Which one of the four types of extinguishers most commonly used? ›

Multipurpose dry chemical fire extinguishes are the most commonly used fire extinguisher because they can put out so many different types of fires. These fire extinguishers are typically for Class K fires. Some of these fire extinguishers can also put out Class A fires. These extinguishes are for Class B and C fires.

How do I choose a fire extinguisher? ›

Every household extinguisher is labeled A, B, or C, which tells you the types of fires the extinguisher is effective against. A is ordinary combustibles like wood, paper, and cloth; B is flammable liquids, such as gasoline or cooking oil; and C is live electricity.

What type of fire can be put out with water? ›

Class A Fires—This kind of fire involves combustibles such as wood, paper, cloth, rubber, trash and plastics. Class A fires are most used for bonfires, camping stoves and other controlled circ*mstances. This is the easiest to put out because the most effective extinguishing agent is water.

Which type of fire extinguisher is the most commonly found type? ›

Dry Chemical extinguishers: Dry chemical extinguishers are the most common and available in few types. These extinguishers will be marked for the classes they are designed to extinguish (e.g., ABC type extinguisher will put out Class A, B and C fires).

What type of fire extinguisher is best for electrical fires? ›

In the case of electrical fires, also known as energized electrical fires, class C fire extinguisher is needed to put it out.

What is the OSHA code for fire extinguishers? ›

OSHA requires a minimum-rated 10B fire extinguisher be provided within 50 feet of the point of job site use of more than 5 gallons of flammable or combustible liquids or 5 pounds of flammable gas.

What is the OSHA rule for fire extinguisher placement? ›

A fire extinguisher, rated not less than 10B, shall be provided within 50 feet of wherever more than 5 gallons of flammable or combustible liquids or 5 pounds of flammable gas are being used on the jobsite. This requirement does not apply to the integral fuel tanks of motor vehicles.

How each types of extinguishers are coded? ›

Fire extinguisher colour coding

Water fire extinguishers are colour coded red. Foam fire extinguishers are colour coded in cream. Powder fire extinguishers are colour coded with blue. Carbon dioxide fire extinguishers are colour coded with black.

How many seconds does a fire extinguisher last? ›

Many portable extinguishers discharge completely in as few as 8 to 10 seconds.

Top Articles
Latest Posts
Article information

Author: Clemencia Bogisich Ret

Last Updated:

Views: 5999

Rating: 5 / 5 (60 voted)

Reviews: 83% of readers found this page helpful

Author information

Name: Clemencia Bogisich Ret

Birthday: 2001-07-17

Address: Suite 794 53887 Geri Spring, West Cristentown, KY 54855

Phone: +5934435460663

Job: Central Hospitality Director

Hobby: Yoga, Electronics, Rafting, Lockpicking, Inline skating, Puzzles, scrapbook

Introduction: My name is Clemencia Bogisich Ret, I am a super, outstanding, graceful, friendly, vast, comfortable, agreeable person who loves writing and wants to share my knowledge and understanding with you.