For the purpose of this section vented cladding shall include the following minimum clear airspaces. Other openings with the equivalent vent area shall be permitted.
- Stucco with a 3/8-inch clear airspace with 3/8-inch continuous slot vent openings at the top and bottom of each wall.
- Brick with a 2-inch clear airspace behind the brick with vents at both the top and bottom of the brick. The vents shall be 3/8-inch × 2.5 inch openings every third brick at both the bottom and top.
- Stone or masonry veneer with a 2-inch clear airspace behind the stone with vents at the top and bottom. The vents shall have at least 1 square inch of vent area for every 24 inches of wall.
- Panel siding with 3/8-inch clear airspace with 3/8-inch continuous slot vent openings at both the top and bottom of each wall.
- Wood, wood based, or fiber cement siding with either a 1/4-inch clear airspace; or alternatively a 1/4-inch gap between the horizontal siding laps.
- Vinyl lap siding applied directly to a weather resistive barrier.
- Manufactured stone veneer with a 3/8-inch clear airspace with 3/8-inch continuous slot vent openings at both the top and bottom of each wall.
- Other approved clear air spaces and vented openings.